Delta Modulon 25 - 200Kva  

The Modulon DPH supports ultimate availability for datacenter operations and provides the benefit of “pay as you go” without over-sizing the UPS. While achieving ultimate availability, the Modulon DPH does not compromise on power efficiency performance. When availability, efficiency and expanding according to business needs are essential, the Modulon DPH is the ideal UPS system to provide power protection and total cost of ownership (TCO) savings. 
 
Advanced fault tolerance design achieved by self redundancy to guarantee operation continuity  
Self-synchronization of power and control modules for continuous on-line operation even in the event of control module failure to avoid downtime caused by single point failure  
Hot-swappable key modules and components to ensure Mean Time To Repair (MTTR) close to zero without downtime risk 
Vertical expansion from 25kW to 75/150/200kW supporting N+X redundancy in a single rack enclosure to save footprint  
Parallel expansion up to four units without requiring additional hardware  
Optional Rack-Mount PDC (applicable for 75/150kW models) has flexibility to arrange its UPS's output power feeding according to its connected critical loads.  
Optional built-in battery modules (applicable for 75kW models) at maximum four units (four battery trays each) 
Full rated power (kVA=kW) to maximize power availability  
High operating efficiency of 95% at 30% light load and 96% from 50% load resulting in marked energy cost savings  
Low harmonic pollution (iTHD<3%) to reduce upstream investment costs and meet demanding power requirements  
Built-in manual bypass features to eliminate maintenance-related downtime  
Proactive detection of fan failure and switch fault for early diagnosis on UPS malfunction  
Plug and play modularity to simplify the maintenance process 
 
 
Call us Now on 0800 999 3300 for No Obligation Quotation  
Delta Modulon Key Technical Data  
Model 
DPH 75kW System 
DPH 150kW System 
DPH 200kW System 
Power Rating 
DPH 75kW System 
DPH 150kW System 
DPH 200kW System 
 
25, 50, 75 kVA 
25, 50, 75, 100, 125, 150 kVA 
25, 50, 75, 100, 125, 150, 175, 200 kVA 
Input 
Nominal Voltage 
Voltage Range 
Current Harmonic Distortion 
Power Factor 
Frequency 
 
380/220V, 400/230V, 415/240V (3 phase, 4-wire +G) 
176~276 / 305~477 Vac * 
< 3% ** 
> 0.99 
50/60 Hz 
Output 
Voltage 
Output Power Factor 
Voltage Harmonic Distortion 
Voltage Regulation 
Frequency 
Frequency Regulation  
Overload Capacity 
 
 
380/220V, 400/230V, 415/240V (3 phase, 4-wire +G) 
1 (kVA=kW) 
≦ 2% (linear load) 
± 1% (static) 
50 or 60 Hz 
± 0.05 Hz 
≦ 125%: 10 minutes 
≦ 150%: 1 minute 
Interface 
Standard 
 
 
Optional 
 
System communication port x 1, LCM port x 1, Parallel port x 2, Smart slot x 2, Output dry contact x 6, Input dry contact x 2, Battery dry contact x 2, REPO 
SNMP IPv6 card, ModBus card, Relay I/O card, 
Battery cabinet temperature sensor cable, Battery cabinet status detection kit 
Conformance 
Safety & EMC 
 
BSMI, CE, EN62040-1 
Other Features 
Parallel Redundancy and Expansion 
 
Emergency Power Off 
Battery start 
Event Log 
 
Module and system redundancy 
Maximum 4 units 
Local and remote 
Yes 
3000 records 
Efficiency 
AC-AC 
ECO Mode 
 
96% (Tested by TÜV) 
99% 
Environment 
Operating Temperature 
Relative Humidity 
Audible Noise (at one meter) 
Dimensions (WxDxH) 
 
0 ~ 40 ˚C 
0~95% (non-condensing) 
< 62 dBA 
600 x 1090 x 2000 mm 
Weight 
UPS System 
 
 
Power Module 
 
 
Rack-mount PDC 
 
 
Battery Module 
 
75kW System: 310 kg 
150kW System: 320 kg 
200kW System: 350 kg 
75kW System: 32 kg 
150kW System: 32 kg 
200kW System: 32 kg 
75kW System: 32 kg 
150kW System: 32 kg 
200kW System: N/A 
75kW System: 29.5 kg 
150kW System: N/A 
200kW System: N/A 
* Lower range 140/242~176/305 Vac is acceptable under 60~100% loading condition. 
** When input vTHD is less than 1%.