Delta Ultron HPH 20 - 120Kva  

The Ultron HPH is a true online double-conversion UPS offering the best-in-class combination of maximum available power, unbeatable energy efficiency and superior power performance for small data centers and other mission critical applications . With fully rated power (kVA=kW), the Ultron HPH provides maximum available power without de-rating the UPS. Thanks to the three level IGBT topology for both PFC (power factor correction) and inverter, the Ultron HPH features up to 96% AC-AC efficiency. Delta’s advanced digital PFC control also contributes low iTHD < 3% and high input power factor > 0.99 resulting in significant TCO (Total Cost of Ownership) savings. Facilitating increased availability and power performance, the Ultron HPH is an ideal solution for protecting your mission critical operations 
 
Fully rated power (kVA=kW) for maximum power availability  
Leading AC-AC efficiency up to 96% saves energy costs  
Low harmonic pollution (iTHD<3%) and high input power factor (>0.99) reduce upstream investment costs 
Wide input voltage range allows the UPS to operate in harsh electrical environments and extends battery life 
DSP based technology enables reduction in the number of electronic components to lower failure rate  
Redundant auxiliary power and fan design* enhance system reliability 
A wide choice of configurations, such as N+X redundancy and hot stand-by  
Adjustable charging current and charging voltage meet different battery configuration requirements  
Flexible battery configuration optimizes battery investment 
A wide choice of configurations, such as N+X redundancy and hot stand-by  
Adjustable charging current and charging voltage meet different battery configuration requirements  
Flexible battery configuration optimizes battery investment 
 
 
 
Call us Now on 0800 999 3300 for No Obligation Quotation  
Delta Ultron HPH Key Technical Data  
Model 
HPH-20K, HPH-30K, HPH-40K, HPH-60K, HPH-80K, HPH-100K, HPH-120K HPH-20K-BN/B, HPH-30K-BN/B, HPH-40K-BN/B 
Power Rating 
 
[20K]: 20kW 
[30K]: 30kW 
[40K]: 40kW 
[60K]: 60kW 
[80K]: 80kW 
[100K]: 100kW 
[120K]: 120kW 
Input 
Nominal Voltage 
Voltage Range 
 
Current Harmonic Distortion  
Power Factor 
Frequency 
 
220/380 Vac, 230/400 Vac, 240/415 Vac 
[20-40K]: -20%~20% (full load), -40%~20% (70% load) 
[60-120K]: -15%~20% (full load), -40%~20% (70% load) 
< 3% 
>0.99 (full load) 
50/60Hz +/-10Hz 
Output 
Voltage 
Voltage Harmonic Distortion 
 
Voltage Regulation 
Frequency 
Overload Capacity 
 
 
220/380 Vac, 230/400 Vac, 240/415 Vac 
[20-40K] < 1.5% (linear load) 
[60-120K] <2% (linear load) 
± 1% (Static) 
50 or 60 Hz ± 0.05Hz 
≤105 %: continuous 
106% ~ ≤125%: 10 minutes 
126% ~ ≤150%: 1 minute 
>150%: 1 second 
Battery  
Type 
Quantity 
 
In-built Charge Current (Max)  
 
Support SMF/VRLA/Tubular/Ni-Cd 
[20-40K]: 32-50 pcs 
[60-120K]: 32-46 pcs 
[20K]: 5A 
[30/40K]: 9A 
[60K]: 10A 
[80K]: 15A 
[100/120K]: 20A 
 
Interface 
Standard 
 
SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2, Output Dry Contact x 6, USB Port x 1* 
Conformance 
Safety & EMC 
 
CE, IEC62040-1, IEC602040-2 
Other Feayures 
Parallel Redundancy 
Emergency Power Off 
Maintenance Bypass Switch 
 
Yes Max 4 units in Parallel upto 480kW 
Local and Remote 
Yes 
Efficiency 
Online 
ECO Mode 
 
Up to 96% (HPH 40-120K efficiency is tested by TÜV) 
Upto 99%  
Environment 
Operating Temperature 
Relative Humidity 
Audible Noise (at one metre) 
 
 
 
0 - 40 ˚C 
5 - 95% (non-condensing) 
[20K]: < 55 dBA 
[30/40K]: < 60 dBA 
[60-120K]: < 65 dBA 
Physical 
UPS Dimensions(WxDxH) 
 
UPS Weight (with batts) 
 
[20-40K]: 490 x 830 x 1400 mm 
 
[20K-B]: 365 kg 
[30K/40K-B]: 385 kg