UPS battery testing services in Essex
Available 24 hours of every day to fit in with your Critical Power requirements.
Load bank testing
Impedance testing
Our test using a Hioki Impedance meter is based on looking at a cell’s internal resistance. This is proving to be a very reliable indicator of state of health and should offer a cost-effective supplement or replacement solution to load bank testing. Field testing on all types of batteries has proven if a cell’s internal resistance increases to more than 35% above its known base line value, that cell will fail a capacity test.
Conductance testing
Conductance is an indication of a battery’s ability to conduct or produce energy. Using conductance and trending the results with information obtained from our handheld Midtronics conductance meter will provide you with the battery’s state of health by showing a percentage of measurement against the known original values. This will help plan the replacement of batteries before they reach end of life.
Contact Us
- Email: sales@tse-ups.com
- Phone: 0800 999 3300
Unit 3, Honywood Business Park, Honywood Road, Basildon, Essex, SS14 3HW